Products / Servo Control Air Cooled Voltage Stabilizer

AIR COOLED · NATURAL COOLING

Servo Control Air Cooled Voltage Stabilizer

Used to obtain a steady three-phase AC supply within very close tolerances from a fluctuating mains. Finds application in dairy, chemical & process industries and research establishments.

Dairy Industry

Chemical & Process

Research

98.5%

EFFICIENCY

415V ±1%
STABLE OUTPUT
1 Year
WARRANTY
KEY BENEFITS

Why it pays for itself

Up to 70%
Reduction in equipment breakdowns
Depending on input voltage variation and plant working hours — resulting in zero breakdown and better utilisation of manpower & equipment.
5–25%
Energy saving

Depending on the input voltage variation and working hours of the plant.

10–15%
Reduction in MDI

A definite reduction in Maximum Demand Indicator follows installation of the equipment.

10–15%
Improvement in power factor

Achievable as the output supply remains stable.

1 Year
Unconditional guarantee
Warranted unconditionally after installation at site, backed by a widespread service network across most states in India with on-site support.
Balanced or unbalanced
Built to your load
Manufactured for unbalanced or balanced load as per customer requirements, at 98.5% efficiency compared with conventional servo stabilizers.
TECHNICAL SPECIFICATIONS

Specification sheet

LoadUnbalanced Type
Input Voltage360 – 480 V AC (L-L)
Output415 V AC +/- 1% (L-L)
DimmersDimmers for individual phases of low / zero maintenance
Buck-boost TransformerASABA make for individual phases
Correction Speed> 20 V / sec
Auto / Manual FacilityAuto manual facility for individual phases
EfficiencyBetter than 98.5%
CoolingNatural air cooled
Effect on Power FactorNil
Response TimeLess than 10 milli-sec
Waveform DistortionNil
Operating TemperatureUp to 50°C from ambient
ProtectionOver-voltage, under-voltage & short-circuit protection (through MCCB at input), single-phasing preventor, reverse-phasing preventor
Control CardPlug-in type microprocessor LCD-based control system for easy maintenance
MeteringDigital type voltage, current & frequency meters
Operated Frequency47 to 53 Hz
System ConstructionAs per IS 9815-1994
Motor for DimmersAC synchronous motors
Cable GlandCable gland for individual inputs and outputs
WiringMulti-strand copper wiring
Toggle SwitchFor INC or DEC of voltage in manual mode for individual phases
Toggle SwitchAuto / manual selection
EarthingEarthing bolt will be provided
Mains MCCBMCB / MCCB at input side of suitable capacity